Since it seems to be a huge mystery to many people how our power systems work
this article tries to provide an introducory view onto grid power supply
and the used protective equipment. Note that this is not an in depth
article that tries to teach how this systems work or describe them into
detail. You wonât be qualified to design a power supply system or perform
installation after reading this article - please refer to some professional
in this case. Incorrectly used protective equipment might be as good as no
protective equipment at all - so please bear in mind that one should know
how to design and install such equipment safely (and you might even not be
allowed to do so on your own depending on the location you live in).
3 phase power system (400V, 230V)
As of today the most common energy system used in Europe is the 3 phase
alternating current system. One can imagine it as having a generator using
3 poles that are separated by 120 degrees - technically generators usually
have of course more than 3 poles but always a multiple of three. The target
network frequency is usually 50 Hz. There are some other systems in place - for
example for railways - that operate at 16.7 Hz.
One can now imagine that a center pole of all three induction coils has been
connected. The non connected sides are called clockwise L1, L2, L3 (or earlier
R,S,T). They are the so called phase. The side that has been connected
together is called the neutral. Why will be shown later on. The most important
thing when connecting a building or machine to this power system is basically
not which phase is called L1, L2 or L3 but only that they form a clockwise
rotating field - so if one connects L2, L3, L1 or L3, L1, L2 in this order
at the main building connection box everythingâs ok too.
The basic idea is that every phase provides an amplitude of $325V$ between
a phase (L) and the neutral (N). The effective value - also called root mean
square - is calculated easily
[
U_{eff} = \sqrt{\frac{1}{b-a} \int_{a}^{b} U(t)^2 dt}
]
As one can see first the centerline of the squared voltages is calculated,
then the square-root is calculated. One can see this as an effective or mean
voltage level. This leads to the well known $230V$ between phase an neutral.
If one wants to look at the potential between two phases one has to consider
the 120 degree phase shift:
[
U_{L1} = U_0 * sin(\omega * t) \\
U_{L2} = U_0 * sin(\omega * t + \frac{2\pi}{3}) \\
U_{L3} = U_0 * sin(\omega * t + \frac{4\pi}{3})
]
The RMS can now easily be calculated as
[
U_{eff} = \sqrt{\frac{1}{T} \int_0^T (U_{L1} - U_{L2})^2 dt}
]
This leads to the well known $400V$ (or $380V$ depending on the amplitude youâre
assuming) power current.
Why 3 phases and neutral?
The answer is pretty simple. If you calculate the effective sum of all three
phases:
[
\int_0^T U_{L1} + U_{L2} + U_{L3} dt = 0
]
they cancel out each other. This is only possible using three or a multiple of
three phases. This is also the cause why the neutral is called that way - during
optimal load all currents on the neutral wire in an 3 phase electrical system (not in
your home though) should cancel out. Because of this one can build electrical power
systems that do not even have a neutral wire on the grid side (see IT systems in the
next chapter) or use smaller dimensions for the neutral wire than one would
calculate when just adding up currents.
Network frequency - PI regulation of the power grid
TL;DR: This is not required to understand your homes electricity
system but only to understand the power system at a large scale.
For the public system deviations from the targeted 50 Hz are normally kept
below 0.2 Hz. This is done using a combined collection of measures. The first
and most important is of course the primary regulation that tries to
match the amount of primary generated power to the currently requested load.
In case too much power is generated or large loads get dropped the frequency
would rise, in case large loads are attached or generated power is reduced frequency
would fall.
One can imagine this as having a force driving the generator that gets
indirectly transferred to a motor. In case someone now adds a load to the
motor the required force on the generator would increase.
The primary regulation is a proportional regulation.
Then thereâs secondary and tertiary regulation. Theyâre usually used to
do longer term regulation than primary regulation that is capable of reacting
in duration counted in seconds. They both do perform some kind of integral
regulation to compensate constant drift of the load centerline. In case secondary
regulation stays active for a long period (for example when some prognosis was wrong,
a power station failed, wind prognosis was wrong, etc.) tertiary regulation gets
activated manually to make some space at the secondary regulation level or optimize
costs. The manual operation of tertiary regulation as well as the prognosis
play a major role on the electricity market and have a huge impact on the cost
of produced electricity.
Note that regulation usually means to switch on or off large generators or loads
like power stations (gas power stations and reservoir power station being really fast,
nuclear being the slowest with regulation periods in hours so theyâre normally only used
to provide base power) or pumping water in reservoir power stations to consume excessive
power.
In Europe there exists some quartiary regulation thatâs done by Swissgrid. Since the
power systems frequency can be used to provide a timing source for cheap synchronous
clocks which has been really common before the invention of DCF, NTP and GPS based
clocks the time tracked via network frequency is compared to correct UTC. In case
there is a deviation of more than 20 seconds the system tries to increase or lower
the centerline of the network frequency by about 10 mHz to compensate for that error.
This is also done by requesting subtle load and generation changes inside a huge
PI regulation loop.
How earth potential is handled (IT, TN and TT system)
There are three different basic power supply systems that all differ in how neutral
and ground potential is handled. What is the ground potential? The basic idea is that
our earth, all buildings, etc. are not perfect insulators - and on the other hand
they can collect charges like an capacitor. To counter that effect two measures are
typically used: The electrical bonding in which different components are simply connected
via low resistance paths (i.e. wires) so the electrical potential equalizes. This is
for example used to connect all pipes, metal cases, metal bathtubs, steel reinforcement, etc.
to a common potential.
Then there is the grounding in which one connects potential literally to a large rod in the
ground that should provide a low resistance path to earth. Normally bonding and grounding
are connected together - but one has to differ between protective earth and ground
to not interfere with RCD operation (i.e. the bonding used in your home is not allowed
to be connected to earth directly - more on that later).
As one can imagine electrical bonding is already a safety feature - it prevents electrical
shock in case a potential is connected to any touchable surface or pipe and it prevents
electrical shock by charge buildup due to capacitive coupling.
So how are earth an neutral handled on the network side? There are basically 3 different
systems in place. Note that you cannot decide which kind of network youâre building when
connecting to a public grid - this has to match your grid provider.
Isole Terre (IT) system
This is the most basic system in which only the three phases are provided by the network
provider. Earth is connected locally to a ground rod but never ever is connected to the
grid. Such systems normally are pretty small and not commonly seen. The generator
can be but hasnât to be grounded on itâs own.
Terre Terre (TT) system
This is more commonly seen up to the main building connection box. In this case the network
operator supplied three phases (L1, L2, L3) and a neutral connector. The generator as well as
your building are connected to earth.
Terre Neutre (TN) system
This is the most commonly seen system inside buildings. There is a distinction between
TN-C (Terre Neutre Combine), TN-C-S (Terre Neutre Combine Separe) and TN-S (Terre Neutre Separe)
systems. They mainly differ in the way protective earth is connected to the network
and how the building is grounded.
In TN-C the source is grounded to earth and the network supplier provides 4 wires - the
three phases and a neutral that also doubles as protective earth (called PEN). On the consumer
side PEN is connected to neutral side of the network as well as to the PE connection.
This is the common setup that one sees in main building attachment boxes supplied
from the grid operator.
In TN-C-S the network provider routes PEN as described for TN-C to your house
attachment box and separates PE and N wires there. Theyâre routed separately to
your main distribution closet - and are attached to a local grounding rod also
at the main attachment box.
The TN-S systems (the part seen after the separation done for TN-C-S) goes a step
further and separates the PE and N wires at the thought source
and routes them as separate wires to your main attachment box.
As one sees the basic idea is the same everywhere and one can come into contact with multiple
different systems depending on the location of oneâs building. Up till the main connection box
one most of the time sees an TN-C system consisting of 4 wires (L1, L2, L3, PEN). Inside the
main attachment box one separates PE and N - they are both connected directly to PEN - and
does attach a local ground connection - so one seeâs a TN-C-S system. Inside oneâs distribution
cabinets one then sees separate PE and N wires all the time so one sees a TN-S system.
The basic difference between these systems is the point at which PE and N are separated or
if this separation is seen from the point of view of the local system - and of course
where the earth potential is connected. The idea is basically always the same.
The main difference and root cause why one normally separated protective earth and neutral
in the main house attachment closure (or has to do so by local regulations)
is that using a combined PEN can be more dangerous than having N and PE separated. Why is this
the case? Under normal operation one uses 230V effective voltage between each phase and the
neutral. In case the PEN wire is broken on the supplier side all loads are connected to each
other via the N wires inside the building - so theyâre connected in series between two
phases (400V). The potential at a connector is then mainly determined by load resistance
so in worst case one can have 400V connected directly to your power outlet which might destroy
devices and provide a hazard to people interacting with the system. More severe residual current
detection devices and breakers (RCD) do not work anymore with broken earth connection. When having
separated PE and N the probability of both of them being broken is lower so in case the N wire
is broken overvoltage protection - and protective equipment - still works. Because of this
separation between N and PE is normally done at the earliest possible point.
Protective equipment
Miniature circuit breaker (MCB / LS)
Circuit breakers limit the current inside the protected circuit. Note that they do not trip
at the voltage specified but obey a specific curve that determines how long it takes them
to trip at a given current. This curve is normally specified by a letter like A, B or C. The
other rating MCBs have is the current theyâre rated for. A B13 or B16 breaker for example is
having a B timing curve with a 13A or 16A limit. Note these devices are not there to protect
humans but to reduce fire hazard. They normally trip in case of short circuits between phase
and neutral which would form a low resistance connection and thus in theory infinite current.
Though infinite current is not possible wires can only have a limited carrying capacity because
current heats them up. If one operates wires at too high current this can lead to sever damage
and is one of the most common fire causes up to day. To counter that one has to add MCBs
in front of each circuit loop that match the wire diameter (or are rated smaller than the used
wire diameter). The diameters and methods to route wires are regulated - please do not violate
these regulations since they take much detail into account.
Normally one sees a MCB tripping in case of either a damaged cable (short circuit) or a damaged
device. The other common cause in which an MCB trips is overload - if you attach too many
devices to a power network the specific circuit trips.
Note that normally protection is not directly hierarchical. Of course upstream fuses are rated
higher than downstream fuses but theyâre normally not dimensioned as the sum of the downstream
fuses. If you have 10 16A circuit breakers your fuses inside the main attachment box are normally
not rated 160A but theyâre selected according to a given parallelity factor or a given booked
maximum current. Because of this itâs entirely possible that upstream fuses blow even if the
downstream MCBs are not.
There are basically two types of MCBs: Ones that only switch the phase and ones that switch
phase and neutral. The switching of the neutral is required for some areas like bathrooms
and is a good idea also in the general case.
Residual current operated circuit breaker (RCCB / RCD / FI)
The residual current operated circuit breaker is a protective device that protects human beings
due to insulation fault. Itâs a simple system that sums up all current flowing through the device.
In case the sum deviates too large from zero the device breaks - normally with currents as low as 25 to
50 mA. The protective effect happens because of protective earth. The RCCB basically only sums up current
between L1, L2, L3 and N. Protective Earth is routed around the RCCB and never has to be connected to
the neutral loop downstream of the RCCB. In case any insulation fault happens or someone touches
a live wire current flows through earth back to the network (since N and PE are connected in your
house attachment box). Since current does not flow through the RCCB the sum of currents is
not zero any more and the device trips.
The summation of currents is done for non electronic monitoring devices in a pretty simply way: All
four wires are routed through a transformer ring. Another wire that senses the sum current is wound
onto the transformer ring - the induced current is tripping the circuit breaker in case itâs reaching
a given threshold. Depending on the system design this transformer can be sensitive to
AC current only (type AC) or also to pulsed direct current (type A). Type AC should not be used
for most installations anymore since itâs design also prevents function in case of overlayed
direct current which can drive the transformer core into saturation and thus prevent
imbalances from triggering the switch - because of this theyâre also forbidden in some
European countries, for example in Germany. Type A RCDs are the most commonly seen as
theyâre capable of protecting against most failure scenarios seen in household and most
industrial settings - and theyâre pretty cheap to manufacture. Note that type A RCDs
may stop to function in case of too large phase shift - this is also another reason
why itâs not allowed to operate devices that do too much phase shifting (like a huge
number of fluorescent lamps in series, huge capacitors, etc.) without power factor correction
directly on the network.
Since they work based on transformers RCDs of type AC and A are usually omnidirectional - it
doesnât matter if power feed goes in on the top and exits on the bottom or the other
way round.
There are currently three additional RCD types available - namely B, B+ and F.
Type B and B+ are triggering electronically and not electromechanically any more. They
do provide protection against non pulsed discrete current, alternating current and work
independent of phase shift between voltage and current. Currently theyâre not seen
that often since they do require a substantial amount of logic that raises cost. Theyâre
often seen in laboratories though where theyâre also required by regulations in some
countries. Type B+ also protects against higher frequency failure currents up to 20 kHz.
Note that since type B and B+ RCDs use electronic components theyâre usually not
omnidirectional any more. Refer to the manufacturers instruction when in doubt.
Type F is the most seldom seen RCD - it can be seen as an extension of a type A
residual current detection device thatâs also sensitive up to 1 kHz of failure
currents and is used in case of variable frequency drives since theyâve higher
frequency effects on the power grid.
Note that these devices should be tested regularly. Testing is done via an integrated test button that
connects phase on one side to neutral on the other side of the switching equipment. One should do this
test at least once a year to detect mechanical fault.
Residual current monitoring (RCM)
RCM is a method not seen in households. The difference to RCCBs is that residual current is only monitored
and detected. This is often seen in data centers and sometimes in industry. This allows one to monitor
slow degrading of insulations or capacitors and replace equipment without unplanned large scale outages.
Selectivity when using residual current circuit breakers
A question that often arises is what happens when one uses residual current
detection devices in series. This is when selectivity gets relevant. All RCCBs
operate at a given tripping current with a specified minimum and maximum
time constant. When building systems serially one can either aim partial selectivity
at which one selects upstream RCDs to be at least two times slower than
downstream RCDs or absolute selectivity by which downstream RCDs maximum
reaction time is lower than the upstreams minimum reaction time.
Note that leakage current of course builds up with wire length and the number
of machines (especially heavy machinery) connected so one also has to take
that into account when designing the protection system.
NH fuses in the house connection box
Technically these do not belong to the consumer side. NH fuses are normally
used in the house connection box in front of the electricity meter. Sometimes
additional fuses - many times enclosed in round packaging that can be screwed
into their receptible - are used in front of meters but after NH fuses in
multi-apartment buildings so that tripping the fuses in front of the metering
device does not trip the whole building and such that working on cabling
for a single apartment does not require shutting down the whole building.
NH fuses should not be handled by non-professionals. There is special equipment
that allows one to pick them on their conductive parts even while under power
and that protects the wearer from and current as well as from arcs. Normally
regulations require one to wear special gloves (sometimes integrated into the
tooling) as well as a face shield and sometimes an insulating skirt when working
with these fuses. Note that most of the time theyâre contained in an plumbed
compartment so access is only allowed to professionals from your electrical
network operator or electricity provider.
Arc fault detection device (AFDD)
These are also called fire protection switches in some case. AFDDs try to
electronically detect the build up of arc flashes. This is possible due to
electronics monitoring the frequency spectrum of the flowing current. Since
arcs of squeezed or partially broken cables are one of the most common fire
sources in households these devices are already mandatory in some European countries
like the United Kingdom. Itâs a good idea to use AFDDs - but of course theyâre
costly. Note that they do not detect an arc immediately but most of the time
fast enough to prevent an fire outbreak.
Combined devices
Of course all of the mentioned protective equipment might also be combined and
applied in multiple levels. To make this somewhat easier there are some
combined RCD and miniature circuit breakers available that are way more costly
than traditional RCDs and mostly type A but allow one to secure every loop
with itâs own RCD. Theyâre mostly used as a second level RCD beyond a selective
upstream one.
This article is tagged: How stuff works, Tutorial, Power grid